Overhead Twisted Cable Type NFA2XSY-T

OVERHEAD TWISTED CABLE

  • ALUMINIUM CONDUCTOR,
  • XLPE INSULATED,
  • COPPER WIRES SCREENED AND PVC SHEATHED
  • Type NFA2XSY-T

Feature
XLPE insulated twisted cables are applied for specially overhead installation.

CONSTRUCTION

Conductor
Stranded compacted circular aluminium conductors. All internal interstices of trie conductor rilled with water blocking compound which is specified to prevent ingress of water through conductor during storage, handling, installation and operating of the cable.

Conductor Screen
Extruded Semi-conducting compound. Minimum thickness 0.5 mm and the maximum volume resistivity of 5000 ohm-cn at 20° C and 25000 ohm-cm at 90° C.

Insulation
Extruded XLPE with high degree of cross-linking, free from contaminants, air voids and heat resistant by dry cured process.

The nominal thickness as shown in table 1.

Type   NFA2XSY-T
Nominal Voltage   3.6/6 ( 7.2 ) kV
6/10 ( 12 ) kV
8.7/15 ( 17.5 ) kV
12/20 ( 24 ) kV
18/30 ( 36 ) kV
Specification   SPLN 43-5
(Other Specifications are availible upon request)

Table 1. Insulation Thickness

Tabel 2 . Minimum Total Cross Section Of Metallic Scree

Insulation Screen
Extruded Semi-conducting compound. Minimum thickness 0.5 mm and the maximum volume resistivity of 5000 ohm-cm at 20°C and 25000 ohm-cm at WC The screen is tightly fitted to insulation to exdude all air voids and can be easily hand stripped on site.

Conduction Water Blocking Layer
Semi-conductive water blocking tape provided over the insulation screen which will swell up under the influence ofmoisture or water.

Metallic Screen
Copper wires applied over the conducting water blocking layer. Minimum cross section of concentric conductor as shown in table 2. Copper tape with minimum thickness 0.1 mm and maximum 0.3mm applied over copper wires.

Water Blocking Layer
Non-conducting water blocking tape provided the metallic screen which will swellup under ihe influence of moisture or water.

Outer Sheath
Extruded black PVC, suitable tar exposure to sun-light or other local atmospheric environments and for the operating temperature of the cable.

Messenger
Stranded galvanized steel wire with 19 wires and cross section 50 mm2, Insulated by extruded PVC which capable for operating continuously at maximum temperature of the cable. Nominal insulation thickness is 1.2 mm.